Copper and Silver Sensor for Purafil OnGuard by Business Empire (info@bempire.co.in)

The OnGuard 4000 (OG4) uses quartz crystal microbalance (QCM) sensors plated with copper and silver to detect corrosion film growth. Purafil Each sensor is designed to be replaced when cumulative corrosion reaches approximately 4, 000 Å (Angstroms). Purafil +2 Purafil +2 When you install a replacement sensor, it must go to the same slot (upper for copper, lower for silver). The unit then performs an initialization period (~2 hours) before giving valid readings again. Purafil +2 SIS - Spécialité Industriel Sherbrooke +2 The sensors are factory calibrated; you do not need to (and should not) manually calibrate them.